Skip to content
CampingCalc

12 V Wire Gauge Calculator: What size wire does the circuit need?

A 1,500 W inverter draws about 140 A at 12 V – over 6.5 ft (2 m) of wire that needs 2 AWG (35 mm²) to keep the voltage drop under 3%. This calculator determines the calculated minimum cross-section and the next standard size for load and charging circuits in your RV.

Important: the result covers voltage drop. The wire's ampacity and the correct fuse must additionally be checked against manufacturer data and codes.

Units

Distance battery → load; the return conductor is included automatically.

Common recommendation: 3% for loads, 1–2% for charging circuits (solar, DC-DC charger).

Advanced settings

Result

Recommended minimum wire size

6 AWG (13.3 mm²)

calculated 8 AWG (8.5 mm²) at max. 3% voltage drop

Calculated cross-section
8 AWG (8.5 mm²)
Voltage drop with standard size
0.246 V
Current
30 A
Total conductor length (out + return)
20 ft
  • The gauge from the voltage drop is a minimum. Ampacity (heating), installation method and fusing must additionally be checked against manufacturer data and codes – no installation approval.
Show calculation
  1. 1Permissible drop: 12.8 V × 3% = 0.384 V
  2. 2Cross-section: 2 × 10 ft × 30 A ÷ (56 × 0.384 V) = 8 AWG (8.5 mm²)
  3. 3Next standard size: 6 AWG (13.3 mm²) → actual drop 0.246 V (1.9%)

 

How it's calculated

The calculator solves the voltage drop formula for the cross-section. You specify how much voltage may be lost in the wire at most.

A [mm²] = 2 × L [m] × I [A] ÷ (κ × ΔU_max [V])
κ (copper, 68 °F / 20 °C) = 56 m/(Ω·mm²); ΔU_max = system voltage × permissible fraction. Example: 2 × 3 m × 30 A ÷ (56 × 0.384 V) = 8.4 mm² → 8 AWG (8.37 mm²)

The calculated value is rounded up to the next standard size. With US units these are the common AWG sizes 18 … 4/0 AWG; with metric units the IEC 60228 series 1.5 · 2.5 · 4 · 6 · 10 · 16 · 25 · 35 · 50 · 70 · 95 mm².

Guidance: AWG size at 3% voltage drop on 12.8 V, one-way length (copper, 68 °F); in parentheses the calculated value in mm²
Current6.5 ft (2 m)13 ft (4 m)20 ft (6 m)
10 A14 AWG (1.9)12 AWG (3.7)10 AWG (5.6)
30 A10 AWG (5.6)6 AWG (11.2)4 AWG (16.7)
60 A6 AWG (11.2)4 AWG (22.3)2 AWG (33.5)
120 A4 AWG (22.3)1/0 AWG (44.6)2/0 AWG (67.0)
Two criteria determine the gauge: voltage drop (this calculator) and ampacity (permissible heating depending on wire type, installation method, bundling and temperature – tables of the wire manufacturer, ABYC E-11 or NEC). The larger of the two applies. Every wire must be fused close to the battery so that the fuse protects the wire.

Worked example

A 2,000 W inverter (90% efficiency) is connected to a 12.8 V LiFePO4 with 5 ft (1.5 m) of wire; permissible voltage drop 2%.

Inputs

  • System voltage: 12 V (LiFePO4 12.8 V)
  • Specify current as: Power in W (e.g. inverter)
  • Power: 2,000 W
  • Efficiency (for inverters): 90 %
  • One-way wire length: 4.92 ft
  • Permissible voltage drop: 2 %
  • Conductor temperature (copper conductivity): 68 °F / 20 °C – κ = 56 m/(Ω·mm²)

Result

1 AWG (42.41 mm²)

Recommended minimum wire size

Calculated cross-section
2 AWG (36.33 mm²)
Voltage drop with standard size
0.219 V
Current
173.6 A
Total conductor length (out + return)
9.8 ft

Calculation

  1. Current: 2,000 W ÷ (12.8 V × 90%) = 173.6 A
  2. Permissible drop: 12.8 V × 2% = 0.256 V
  3. Cross-section: 2 × 4.9 ft × 173.6 A ÷ (56 × 0.256 V) = 2 AWG (36.33 mm²)
  4. Next standard size: 1 AWG (42.4 mm²) → actual drop 0.219 V (1.7%)

The variables explained

Continuous current (A)
Maximum current flowing continuously. For inverters calculated from power, voltage and efficiency.
One-way wire length
Distance from the source to the load; the return conductor is included automatically.
Permissible voltage drop (%)
3% for loads, 1–2% for charging circuits are common recommendations – not a vehicle code, but proven practice.

Common mistakes

  • Sizing the wire only for voltage drop and forgetting ampacity: short runs with high current (inverter) can still get too hot at low drop if the wire is bundled or enclosed.
  • Choosing the fuse for the load instead of the wire: the fuse protects the wire – it must match the gauge and sit close to the battery.
  • Calculating cheap CCA wire (copper-clad aluminum) with copper values – it has about 35% less conductivity.
  • Mixing up AWG and mm².

Assumptions and limits

  • Copper conductor, conductivity 56 (68 °F / 20 °C) or 48 (158 °F / 70 °C) m/(Ω·mm²).
  • Standard sizes up to 4/0 AWG (107 mm²) or 95 mm²; larger currents require parallel conductors or a 24 V system.
  • No assessment of ampacity or fusing – manufacturer data and codes apply. Electrical installations should be checked by a professional.

Frequently asked questions

What size wire do I need for a 2,000 W inverter?

At 12.8 V and 90% efficiency about 175 A flows. For 5 ft (1.5 m) of wire and 2% voltage drop the calculator gives 36 mm² calculated, i.e. 2 AWG (33.6 mm²) isn't quite enough and 1/0 AWG (53.5 mm²) is the next common size; many manufacturers specify 2 AWG to 1/0 AWG for this power class. The inverter manufacturer's specification is binding.

Is 14 AWG (2.5 mm²) enough for a refrigerator circuit?

For 5 A over 20 ft (6 m) one-way length the result is 14 AWG at 3% drop. Compressor fridges are sensitive to low voltage – 12 AWG (4 mm²) is the safer choice on longer runs.